The specific character of an automatic control system of VCS operation is using of several clappers of water feeding into the condenser which open/close depending on vacuum and also on temperatures of effluent gases and water that allows minimizing quantity of water consumption.
If the automatic control system of VCS is used simultaneously with automatic control system of sugar end division the water feeding is partly changed for preventive alignment of vacuum in collector at starting and stopping of a recurrent vacuum set.
|
Example of VCS operation |
||
|
Parameter |
Preheater of 2nd group + |
Preheater of 1stgroup + Condensers B and C |
|
Quantity of condensed steam, t/h |
20 ÷75 |
7÷20 |
|
Absolute pressure of steam, MegaPascal |
0,02…0,017 |
0,01…0,014 |
|
Initial temperature of clean manufacturing water (tн), ºС |
4÷20 |
- |
|
Initial temperature of diffusion juice (tсн), ºС |
43 |
27 |
|
Final temperature of diffusion juice (tск), ºС |
58÷59 |
43 |
|
Final temperature of clean manufacturing water (tн), ºС (tк), ºС |
58÷60 |
- |
|
Initial temperature of rewater (tн),ºС |
30 |
30 |
|
Temperature of non-condensed gases (tг),ºС |
32 |
32 |
|
Aerodynamic resistance of steam, KiloPascal |
no more than 1,5 |
no more than 1,5 |